上海新上化高分子材料有限公司

Your current position:Home > Products > Peroxide XLPE Compound

Peroxide XLPE Compound
Extra-Clean XLPE Compound for 10KV and Below Power Cable

Main Properties & Typical Values

Test Items

Unit

Test Method

Standard

Typical value

Tensile strength

MPa

GB/T1040.3

≥13.5

24.7

Elongation at break

%

GB/T1040.3

≥350

521

Heat ageing properties (Test temperature 135℃, 168hr)

Maximum tensile strength change      

Maximum elongation at break change

 

%

%

 

GB/T8815

 

±20

±20

 

12

3

Heat elongation (200±3)℃x15minx0.2MPa)

Maximum elongation change under load      

Maximum permanent elongation change after cooled 

 

%

%

 

GB/T2951

 

≤80

≤5

 

40

2

Impact brittle temp. (-76℃)   

Impact brittle

Failure no.

GB/T5470

 

≤15/30

 

pass

Dielectric Strength

MV/m

GB/T1408.1

≥25

36

Dielectric loss factor 50Hz, 20℃

--

GB/T1409

≤5×10-3

3.1×10-4

Dielectric constant 50Hz, 20℃

--

GB/T1409

≤2.35

2.27

Volume resistance (20℃)

Ω·m

GB/T1410

≥1×1014

2.1×1014

Gel content

%

JB/T10437

≥80

85

 

Note: All typical values were tested by press moulding sample under the condition of 180±2 ℃,15min, and pressure over 15Mpa, then cooling to room temperature.

Shanghai New Shanghua Polymer Material Co.,Ltd.
Add: NO.55,XinhanRoad,Xinchang Industrial Zone,Pudong Shanghai Tel:021-65193960 Fax:021-65707269